Technical resources

Tank capacity and plant-room layout

Record the required working capacity, makeup conditions and minimum operating level.

Tank capacity and plant-room layout
Illustrative scene

Project checks

  1. Record the required working capacity, makeup conditions and minimum operating level.
  2. Mark doors, columns, pipes, manhole direction and access in plan and set foundation, roof and invert elevations in section.
  3. Put inlet, outlet, overflow, drain, vent and level points on the same drawing. Refer full-water loading to the structural team.

Rectangular and L-shaped volume

Multiply clear internal length by width for a rectangle. For an L shape, subtract the cutout from the enclosing rectangle. A 4 × 3 m internal envelope with a 1 × 1 m cutout has a clear plan area of 11 m². At a 1.5 m working depth it provides 16.5 m³ before displacement, 1.5 m³ less than the full rectangle. Calculate sloping bases or changing cross-sections in bands.

Comparing layouts

Mark the same operating levels, clear door openings and underside of beams on both drawings. Check service clearance for the rectangular layout first. Where a column obstructs the layout, assess an L shape and verify additional corners, seams, bracing, complete drainage and cleaning access.

Cross-checking the purchase schedule

Record external and clear internal dimensions, operating levels, connection elevations, material and thickness by course. Check foundation and structural loads at full water level and withdrawal conditions at the lowest operating level. For potable storage, verify the applicable hygiene documents and the product models they cover.