In October 2008, low rainfall dropped the Xiang River level and algae clogged filters at some Xiangtan and Zhuzhou waterworks. Xiangtan’s utility said the worst conditions shortened backwash intervals from 24–36 hours to about two hours, affecting supply to parts of the east bank. Plants in both cities increased raw and treated water monitoring.
Engineering takeaway Track intake conditions, filter operation and delivery capacity during raw-water changes.